Description
Energy Meters are typically used in an Energy Storage System, to measure the power and energy of the entire application at the distribution box and minimises energy import or export to the grid. They can also be used to measure the output of a PV inverter or AC loads and display the data on GX devices such as the Cerbo GX or Ekrano GX and the VRM Portal.
Key Features
- Three-phase energy meter with Ethernet and VE.Can communication ports
- Designed for measuring power and energy in single- and three-phase applications, such as distribution boxes or PV Inverters
- High refresh rate for accurate measurements of RMS power values transmitted over VE.Can or Ethernet
- Easy setup with Plug & Play functionality as a grid meter for most systems; configuration via VictronConnect for role changes (Grid Meter, PV Inverter, AC Genset, or AC Load Meter) and manual IP configuration
- Remote monitoring available through VictronConnect App, Cerbo GX, Ekrano GX, and VRM Portal
- Effortless installation using snap-on type current transformers, eliminating the need to modify existing wiring
- Utilizes vector registration method, summing the vectors of each phase (L1, L2, and L3) for precise measurements.
Specifications
- Model: VM-3P75CT REL200300100
- Voltage connection: Direct
- Input voltage range L-N: 85 to 265VAC
- Input voltage range L-L: 150 to 460VAC
- Frequency: 50/60Hz
- Current connection: Via current transformers (included – wire length 640mm)
- Rated current: 75A
- VE.Can communication port: Two RJ45 connectors (VE.Can terminators included)
- Ethernet communication port: One RJ45 connector, Modbus UDP
- Refresh rate: 100ms
- Type: Self-power supply via L1-N
- Consumption: 1.45W / 3.1VA
- Frequency: 50/60Hz
- Material & Colour: Polycarbonate, blue (RAL 5012)
- Voltage connection: Screw terminals 0.25 – 1.5mm2 (24 – 16 AWG)
- Current transformer connection: Pluggable screw terminals (included)
- Protection category: IP20
- Weight: 370g (including packaging)
- Dimensions (h x w x d): 90 x 71 x 59mm (3.5 x 2.8 x 2.3in)
- Indoor/outdoor usage: Indoor only
- Operating temperature: From -10 to +55 °C
- Storage temperature: From -20 to +70 °C
- Relative humidity: < 90 % non-condensing
- Altitude: 2000m (6562ft)
- Mains supply voltage fluctuations: ±0.1Vin
- Overvoltage category: Cat. III
- Pollution degree: 2
- Safety: EN-IEC 61010-1